What Size Wire for a 40 Amp Breaker?

A 40 A breaker needs 8 AWG copper or 8 AWG aluminum with 75°C terminations (NEC Table 310.16). Longer runs may need a size up for voltage drop: distances below.

Minimum wire size for 40 amps

ApplicationCopper (75°C)Aluminum (75°C)
Branch circuit / feeder (Table 310.16)8 AWG8 AWG
Worth knowing: 8 AWG copper carries exactly 40 A in the 60°C column, so 8/3 NM-B is the last size where cable and conduit still agree.

Assumes 75°C-rated terminations (NEC 110.14(C)). Both assume no more than three current-carrying conductors in a raceway at 30°C ambient. Derating, continuous loads, and local amendments can change the answer: confirm with a licensed electrician.

Ground wire for 40 amps

GroundCopperAluminum
Equipment ground (bare / green) (Table 250.122)10 AWG8 AWG

The equipment ground is sized by the breaker, not the load: a 40A breaker falls in Table 250.122's 60 A row. Upsize the hots for voltage drop and the ground must grow in proportion (NEC 250.122(B)). Every size, with a worked upsizing example, is in the ground wire size chart.

How far can you run it? (voltage drop)

Keeping voltage drop under the recommended 3% at a 32 A load (80% of the breaker), 8 AWG copper is good for roughly:

System voltageMax one-way run (8 AWG Cu)
120 V≈ 71 ft
240 V≈ 143 ft

Past these distances, step up one gauge. Run your exact length and load through the voltage drop calculator.

What runs on 40 amps

  • Electric range
  • 32 A EV charger
  • Larger AC condensers

Common receptacle at this rating: NEMA 14-50.

Parts for a 40 A circuit

A plug-in EV charger on a 40 A circuit can draw up to 32 A for hours a night: the NEC treats it as a continuous load at 80% of the breaker. Use a heavy-duty 14-50 receptacle built for that duty, not a residential-grade range outlet. Both picks take copper conductors only, so an aluminum run needs a device listed for aluminum.

We earn a commission if you buy through links on this page, at no extra cost to you. It does not change what we recommend. See our affiliate disclosure. As an Amazon Associate I earn from qualifying purchases.

All receptacle picks

Frequently asked questions

8 AWG copper with 75°C terminations (NEC Table 310.16). In aluminum, use 8 AWG. Longer runs, high ambient temperatures, or bundling can require upsizing.

Ask AI about this

Open an AI assistant with a question grounded in this page.

Full wire & breaker chartVoltage drop calculatorGround wire size chartEV charger breaker sizing

Other amperages

Cite or link to this pageAPA · MLA · Chicago · HTML

Free to cite, quote and link. Copy a ready-made citation: the link back is all we ask.

APA

WattSimple. (2026, August 16). What Size Wire for a 40 Amp Breaker? https://wattsimple.com/wire-size/40-amp

MLA

"What Size Wire for a 40 Amp Breaker?" WattSimple, 16 Aug. 2026, https://wattsimple.com/wire-size/40-amp.

Chicago

WattSimple. "What Size Wire for a 40 Amp Breaker?" Last modified August 16, 2026. https://wattsimple.com/wire-size/40-amp.

HTML link

<a href="https://wattsimple.com/wire-size/40-amp">What Size Wire for a 40 Amp Breaker?</a> (WattSimple)