Ground wire size chart

Two different NEC tables answer “what size ground wire”: the ground that runs with a circuit is sized by its breaker, and the ground to the rods is sized by the service conductors. Both are below, copper and aluminum.

Ground wire for common circuits

Equipment grounding conductor (the bare or green wire) by breaker size, from NEC Table 250.122.

BreakerCopper groundAluminum groundTypical use
15 A14 AWG12 AWGLighting, general outlets
20 A12 AWG10 AWGKitchen, bath, garage outlets
30 A10 AWG8 AWGDryer, water heater
40 A10 AWG8 AWGRange, 32 A EV charger
50 A10 AWG8 AWGRange, NEMA 14-50, 40 A EV charger
60 A10 AWG8 AWG48 A EV charger, subpanel
70 A8 AWG6 AWGSubpanel, heat pump
100 A8 AWG6 AWGSubpanel feeder
125 A6 AWG4 AWGLarge subpanel feeder
200 A6 AWG4 AWG200 A feeder

Equipment grounding conductor (NEC Table 250.122)

Find the first row at or above your breaker or fuse rating: a 30 A breaker uses the 60 A row.

Breaker or fuse, not exceedingCopperAluminum or copper-clad Al
15 A14 AWG12 AWG
20 A12 AWG10 AWG
60 A10 AWG8 AWG
100 A8 AWG6 AWG
200 A6 AWG4 AWG
300 A4 AWG2 AWG
400 A3 AWG1 AWG
500 A2 AWG1/0 AWG
600 A1 AWG2/0 AWG
800 A1/0 AWG3/0 AWG
1,000 A2/0 AWG4/0 AWG
1,200 A3/0 AWG250 kcmil
1,600 A4/0 AWG350 kcmil
2,000 A250 kcmil400 kcmil
2,500 A350 kcmil600 kcmil
3,000 A400 kcmil600 kcmil

Shown to 3,000 A; the code table continues to 6,000 A for large commercial and industrial services.

Upsized the hots for voltage drop? Upsize the ground too

NEC 250.122(B): when the hot conductors are made larger than the minimum to cut voltage drop on a long run, the equipment ground must grow by the same ratio of circular-mil area. Most charts skip this rule, and it is the one that catches long subpanel and detached-garage feeders.

Example: a 50 A feeder would normally use 8 AWG copper hots (16,510 circular mils) with a 10 AWG copper ground (10,380 cmil). Over a long run you step the hots up to 6 AWG (26,240 cmil), a factor of 1.59. The ground must then be at least 10,380 × 1.59 = 16,500 cmil, which is 8 AWG copper, not 10.

The ground never has to be larger than the circuit's own hot conductors (NEC 250.122(A)). Circular-mil areas are from NEC Chapter 9, Table 8. Check a run with the voltage drop calculator.

Grounding electrode conductor (NEC Table 250.66)

The wire from the service equipment to the ground rods, concrete-encased (Ufer) electrode or water pipe. Sized by the largest hot service-entrance conductor, not the breaker.

Service conductor, copperService conductor, aluminumCopper GECAluminum GEC
2 AWG or smaller1/0 AWG or smaller8 AWG6 AWG
1 or 1/0 AWG2/0 or 3/0 AWG6 AWG4 AWG
2/0 or 3/0 AWG4/0 AWG or 250 kcmil4 AWG2 AWG
Over 3/0 AWG – 350 kcmilOver 250 – 500 kcmil2 AWG1/0 AWG
Over 350 – 600 kcmilOver 500 – 900 kcmil1/0 AWG3/0 AWG
Over 600 – 1100 kcmilOver 900 – 1750 kcmil2/0 AWG4/0 AWG
Over 1100 kcmilOver 1750 kcmil3/0 AWG250 kcmil
  • A typical 200 A dwelling service on 2/0 copper or 4/0 aluminum needs a 4 AWG copper grounding electrode conductor.
  • To ground rods, pipe or plate electrodes alone, the conductor never has to be larger than 6 AWG copper or 4 AWG aluminum (NEC 250.66(A)).
  • To a concrete-encased (Ufer) electrode alone, it never has to be larger than 4 AWG copper (NEC 250.66(B)).

Notes

  • Values are code minimums from the 2023 NEC. Your jurisdiction may have adopted an earlier edition or local amendments.
  • Table 250.122 is a floor: the ground must also be large enough to clear a fault quickly (NEC 250.4), which can call for a larger conductor on very long runs.
  • Grounding and bonding errors are a shock and fire hazard. Have a licensed electrician do the work and pull the permit, and confirm with your local authority having jurisdiction (AHJ).

Frequently asked questions

8 AWG copper or 6 AWG aluminum. NEC Table 250.122 sizes the equipment grounding conductor by the breaker protecting the feeder, and the 100 A row calls for 8 AWG copper. If the feeder conductors were upsized for voltage drop on a long run, the ground has to be upsized in proportion (NEC 250.122(B)).

Test before you touch

Before working on any circuit sized from this chart, confirm it is dead with a voltage pen. A clamp meter reads the real load on one conductor, which shows how close an existing circuit runs to its breaker. Panel work is for someone qualified, under a permit where your AHJ requires one.

We earn a commission if you buy through links on this page, at no extra cost to you. It does not change what we recommend. See our affiliate disclosure. As an Amazon Associate I earn from qualifying purchases.

All tester picks
Cite or link to this pageAPA · MLA · Chicago · HTML

Free to cite, quote and link. Copy a ready-made citation: the link back is all we ask.

APA

WattSimple. (2026, July 16). Ground Wire Size Chart. https://wattsimple.com/reference/ground-wire-size

MLA

"Ground Wire Size Chart." WattSimple, 16 July 2026, https://wattsimple.com/reference/ground-wire-size.

Chicago

WattSimple. "Ground Wire Size Chart." Last modified July 16, 2026. https://wattsimple.com/reference/ground-wire-size.

HTML link

<a href="https://wattsimple.com/reference/ground-wire-size">Ground Wire Size Chart</a> (WattSimple)